Collected informations for using Modbus on TCP/IP. Libmodbus is used as master on any Linux computer (Sheevaplug). Wago fieldbuscouplers 750-342 (or alternatively 750-841) are used as slaves.
| Code | Bits | Target | Count | Direction | Name in Spec | Libmodbus 3 fkt name | libmodbus 2 fkt name | 
|---|---|---|---|---|---|---|---|
| 01 | 1 | DO | many | read | Read Coils |  modbus_read_bits                 |  read_coil_status           | 
	
| 02 | 1 | DI | many | read | Read Discrete Inputs |  modbus_read_input_bits           |  read_input_status          | 
	
| 03 | 16 | AO | many | read | Read Holding Registers |  modbus_read_registers            |  read_holding_registers     | 
	
| 04 | 16 | AI | many | read | Read Input Register |  modbus_read_input_registers      |  read_input_registers       | 
	
| 05 | 1 | DO | one | write | Write Single Coil |  modbus_write_bit                 |  force_single_coil          | 
	
| 06 | 16 | AO | one | write | Write Single Register |  modbus_write_register            |  preset_single_register     | 
	
| 15 | 1 | DO | many | write | Write Multiple Coils |  modbus_write_bits                |  force_multiple_coils       | 
	
| 16 | 16 | AO | many | write | Write Multiple registers |  modbus_write_registers           |  preset_multiple_registers  | 
	
| 23 | 16 | AI/AO | many | both | Wrt/Rd Multiple registers |  modbus_write_and_read_registers  |    | 
	
More information sources:
Basic principle: The bootp client (750-342) sends its MAC address to the bootp server (eg. a slackware linux computer). The server in turn provides the client with an IP address.
Example: To provide the client host with the name etb-130 who has the MAC address 0030DE010A2C with the IP address 192.168.132.130 and an appropriate subnet mask, add the following line to /etc/bootptab:
etb-130:ht=1:ha=0030DE010A2C:ip=192.168.132.130:sm=255.255.255.0
Then, on the server machine, start the bootp daemon by uncommenting the following line in /etc/inetd.conf
bootps dgram udp wait root /usr/sbin/bootpd bootpd
…and restart the inetd:
/etc/rc.d/rc.inetd restart
Now connect the Client with the server eg over crosslink cable and boot the client.
The 750-342 fetches its IP from the bootp server only when bootp is enabled. Otherwise it uses the IP saved in its EEPROM. Pseudcode:
ipNumber= bootpEnabled ? getIpNumberFromBootpServer() : getIpNumberFromEeprom()
Web access to 750-342 is admin / wago
See also: Wago manual p.82ff and bootptab
Download the source and use the Slack build script.
Note: You could get the latest devel release with git clone http://github.com/stephane/libmodbus.git, but this has no configure script, so we use the lataest stable release instead.
Download v 2.0.3 from here
Libmodbus has the unpleasant behaviour, that it prints error messages to stdout instead of stderr. If you plan to build your application like a filter which commuicates over stdin / stdout to the world, than you will get problems, in that libmodbus may interfere your protocoll or whatever with error messages. Therfore we patch the source a little bit and are writing error messages to stderr instead of stdout. Look for the function error_treat in modbus/modbus.c and replace the printf function with fprintf:
static void error_treat(modbus_param_t *mb_param, int code, const char *string) { printf("\nERROR %s (%d)\n", string, code);
static void error_treat(modbus_param_t *mb_param, int code, const char *string) { fprintf(stderr, "\nERROR %s (%d)\n", string, code);
Now do the usual ./confiure; make; su; make install;. This installs the following objects to /usr/local/:
lib/libmodbus.so lib/libmodbus.la lib/libmodbus.so.2.0.0 lib/pkgconfig/modbus.pc lib/libmodbus.so.2 include/modbus/modbus.h
Then do ldconfig to update the library system info.
uint8_t dest[] array. I.e. each bit consumes one byte.uint16_t dest[] array